Application of plate heat exchanger in radiant heating and cooling

Radiation heating and cooling air conditioning systems have been used and developed in Europe and North America for many years. Unlike traditional convection air conditioning systems, radiative heat and heat transfer systems account for more than 50% of total heat exchange. The air conditioning system based on low-temperature radiation heat transfer works by inputting cold water of about 18 °C into the end of the radiation in summer to form a cold radiating surface; in winter, it provides hot water of about 45 °C to the end of the radiation to form a heat radiating surface, relying on Radiant heat exchange with the human body, furniture and the rest of the enclosure is cooled (heated). If the temperature of the hot and cold water supplied by the cold heat source is too low or too high to meet the radiation end temperature requirements, the plate heat exchanger or other methods (such as water mixing) are usually used to achieve the temperature of the cold (hot) medium. Claim.
First, the application in radiant cooling
When radiant cooling, the temperature of the cold water in the end of the radiation should not be too low, otherwise it will easily produce condensed water at the surface of the radiation, causing condensation. Generally, the method of controlling the temperature of the cold water inlet of the radiation end is adopted, so that the surface temperature of the radiation plate is higher than the air dew point temperature by 1 to 2 ° C to prevent condensation. The chilled water temperature (16-18 °C) used in radiant cooling systems is usually higher than conventional air conditioning systems (7 °C). The higher cold water temperature provides a choice for natural cold sources such as evaporative cooling (6-8 ° C), but It also makes the chilled water produced by the conventional chiller (the supply and return water temperature is 7/12 °C) can not directly meet the requirements of the radiant cooling system for the cold water temperature. Generally, the high temperature required for radiant cooling can be obtained by the method of mixing water. Cold water, but in order to prevent the cold water from directly entering the sensible heat exchange end (especially the capillary) and causing scale on the inner surface of the heat exchanger to block, the high-efficiency plate heat exchanger can be used to carry out the countercurrent heat exchange of the cold water produced by the chiller. Then send it to the sensible heat end. The inlet water temperature commonly used for sensible heat at the time of radiant cooling is 16 to 18 ° C, and the return water temperature is generally 21 to 23 ° C.
Second, the application in radiant heating
The application of plate heat exchanger in low temperature radiant heating is divided into two types: water-water heat exchange condition and steam-water heat exchange condition. When steam is used as the heat source, the steam must be low-pressure saturated steam. The pressure commonly used in engineering is: gauge pressure 0.3MPa or gauge pressure 0.4MPa, the steam temperature at this time is 144 ° C and 152 ° C. When hot water is used as the heat source, the hot water supply back water temperature is generally 95/70 °C. In radiant heating, the temperature of the hot water supplied to the end of the radiation should not be too high, generally not exceeding 60 ° C. The main reasons are:
1. Due to the large radiation area, the water temperature does not need to be too high to meet the room temperature design requirements;
2, the human body comfort requires the ground temperature can not be too high;
3. At higher water temperatures, the life of plastic pipes commonly used in radiant heating is greatly reduced. According to the different requirements of building insulation and occupants, the ground temperature is usually controlled within the range of 24 to 30 °C. Excessive temperature affects comfort and causes unnecessary waste. If the temperature is too low, heating requirements are not met.
In recent years, the state's requirements for building energy conservation have been continuously improved, and the degree of insulation of the envelope structure has become better and better, which has led to a continuous decrease in the actual use of water. Under the premise of common pipe diameter and pipe spacing, the actual required inlet water temperature is often lower than 50 °C. When the outdoor temperature is not too low, the inlet temperature of 30-40 °C can already have obvious heating effect. The inlet and outlet water temperature commonly used in low temperature radiant heating systems is usually 45/35 °C.
2019/05/10 20:08:59 3760 Click

碳酸锂:现货驱动强劲,预期转向下的博弈加剧 遇见小面股价破发 讲好规模故事还差多少火候? 为什么总有人说“上班以后越来越胖”? 近5000万元货款逾期,工业超声设备第一股骄成超声将萨驰股份、吉驰轮胎告上法庭|江苏省 江门:促进农文旅融合高质量发展 三连涨后首度回调,港股通创新药ETF(520880)跌近1%高频溢价!机构:关注“硬创新”+“强出海”创新药资产 知名上市药企,被重罚2560万!|贵州百灵 国台办发言人陈斌华答记者问|国台办 宁德时代与岚图签署十年深化合作协议|宁德时代 驻马店·平舆第二届跨境电商大会开幕 振邦智能:股东中天智科拟减持52000股|智科 业务不审慎,这家券商巨头被罚|海通证券 中国信达新疆分公司能源业务团队:开局之年创佳绩,能源赛道立新功|新疆 AI赋能文化新生态 世纪华通确认参展2025长三角文博会 酒价内参12月22日价格发布 市场创新低水晶剑南春领跌 一周观市|光大保德信基金:继续关注进攻板块,看好科技方向 方跃教授:AI若无法规模化落地,市场或重演2000年互联网泡沫|Alpha峰会 探寻新时代发展足迹|水清岸绿产业兴 洱海绘就新画卷 杰瑞股份:公司从事的主要业务包括高端装备制造、电力业务、油气工程及技术服务等,暂不涉及航天领域 全国火出圈,光峰科技AR光机再次亮相央视 罗莱生活捐赠500万元暖心物资,驰援香港大埔灾后救援